Product DescriptionBrief IntroductionDescription1.Electrical grade insulating cable paper is manufactured from 100% high-quality sulfate insulating wood pulp. Our ordinary insulating papers are available in nominal thicknesses from 50 to 250 microns,a…

Product Description

Brief Introduction
Description
1.Electrical grade insulating cable paper is manufactured from 100% high-quality sulfate insulating wood pulp. Our ordinary insulating papers are available in nominal thicknesses from 50 to 250 microns,
and in continuous rolls up to the widths of 625, 960mm and 1200mm (the roll diameter being 680 to 730mm),
or other customized diameters and widths on request.
2.Insulation Press Paper Board is appropriated for uses as electric industrial board for motors, electric device, instruments, switch board, transformer for insulation and assembly pieces. 100%(wood/cotton) thick board is characterized by its high density, good mechanical strength, low compression coefficient and high electric strength.
3.This paper is highly refined and cleaned to ensure uniform thickness and free from formation Pinholes, un-dispersed fiber bundles and tiny defects
It is a low-voltage grade insulating paper well suited for making electromagnetic wires, power cables of transformers below 35kV and other electrical insulating equipments below 35kV. This paper has stable electrical and chemical properties, and high physical strength to meet the exacting
needs of our valued customers.
Insulation Paper Cable Paper Press Paper for Transformers
 


Specified Properties

Units

Values Specified 




2mil 

2.5mil

3mil

4mil 

5 mil

Thickness Tolerance

Micron


50+/-10%

64+/-10%

75+/-10%

100+/-10%

125+/-10%

Substance (Grammage)

g / m^2


40+/-10% 

51+/-5% 

61+/-5% 

76+/-5% 

100+/-5% 

Apparent Density

g / m^3

0.8 +/- 0.05 

Moisture Content


8 Max

Moisture content


5 - 9

Water Absorption MD
CD

Mm 

10 Min.

Air Permeability

m/Pa.Sec 

0.5 to 1.0

Tensile Index MD
CD

Nm/g

78 Min 
28 Min

Elongation MD
CD

%

2.0 Min
4.0 Min

Tear Index MD
CD

mN m^2/g

5 Min
6 Min

Electric Strength in Air

KV/mm

7.0 Min

Ash Content

%

1.0 Max

Conductivity of 5% Aqueous Extract

Ms/m

10 Max 

Ph of 5% Aqueous Extract


6 - 8 

Heat Stability (150degC,24hrs)

%

20 Max

Features
PropertiesUnitTesting  value
Thicknessmm0.8~1.0mm1.5~2.0mm2.5mm3.0mm
Thickness Tolerance%±7±5
Densityg/cm31.00~1.251.10~1.25
Tensile Strength, Min. CrossN/mm250
Longitudinal90
contraction, Max. Cross%1.4
Longitudinal1.0
Vertical6.0
Elongation, Min. Cross%4.0
Longitudinal35
Dielectric Strength, Min.KV/mm35302724
Humidity%4~95~9
PH of Aqueous Extract
6.0~8.0
Oil-absorbency, Min.%9
 
Applications
Used widely as electrical insulation wrap on aluminium and copper wires by conductor manufacturers,
electrical insulation between layers of wound coils in electrical motors, in capacitors, transformers & such
other electrical equipment.